- Heating and cooling sequence
- 2nd heating sequence
- Selectable P-band (1 K heating, 0.5 K cooling, or 4 K heating, 2 K cooling)
- Selectable dead zone (2 K or 5 K)
- Frost protection function
RCU10 Universal room thermostat for 4-pipe systems, AC 230 V, positioning signal 2 pt or PWM
RCU10 Universal room thermostat for 4-pipe systems, AC 230 V, positioning signal 2 pt or PWM
Low stock: 10 left
Regular price
RM678.00
Regular price
Sale price
RM678.00
Unit price
/
per
Technical Specifications:
Operating voltage |
AC 230 V
|
Power consumption
|
6 VA
|
Setpoint setting range
|
8…30 °C
|
Triac outputs, number
|
2
|
Switching differential
|
Heating: 1…4 K; Cooling: 0.5…2 K
|
Digital inputs, number
|
1
|
Digital input, contact query
|
3…6 mA, 6…15 V
|
Digital input, application
|
Night setback
|
Triac outputs
|
PWM or ON/OFF
|
Triac output, switching voltage
|
230 V
|
Triac output, switching current
|
0.02…1 A
|
Type of fixing
|
Wall mounting with screw
|
Degree of protection
|
IP30
|
Dimensions (W x H x D)
|
97 x 114 x 43 mm
|